Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 17
Programming Steps Programming
3.2.4 Subsidiary Equipment
The panels and network annunciators in this section may be present on an MN network without being part of an ACU, LOC or CCS.
They do not have local control when an MN alarm is active in the system unless fire is the highest priority and there is a fire alarm on the
panel or on a mapped node on the NCA-2. They are capable of initiating and annunciating an MN alarm, but can not perform acknowl-
edge, silence, or reset functions while an MN alarm is active in the system.
DVC-RPU
MN Paging Levels are not installed when the DVC-RPU acts as a subsidiary device.
Program the DVC-RPU label. Refer to “DVC-RPU” on page 33.
MN Annunciator Programming
Program an annunciator as a dedicated MN alarm annunciator (See page 34). Set an LCD2-80 to terminal mode (See page 34). Use DVC
General Zones Z501 - Z533 to annunciate LOC and ACU paging. Refer to “DVC General Zones” on page 34.
4 Create MN audio paging group(s). manual
5 Set up the workstation priorities for an MN CCS station. manual
CCS Programming Steps
Subsidiary Equipment Programming Steps
NFS2-3030*/NCA-2
1 Set the mass notification priority. page 19
2 Set the DCC field. page 18
3 Map to MN nodes. page 23, page 23
4 Program with MN type IDs. page 24
5 Set the MN Control Field to Subsidiary. page 35
6 Program with MN Special Function Zones. page 25
*NFS2-3030 may be in standard or network display mode.
NFS2-640/NFS-320/SYS
1 Set the mass notification priority page 21
2 Set the DCC field. page 18
3 Map to MN nodes. page 24
4 Program with MN type IDs. page 24
5 Program with MN Special Function Zones. page 25
DVC
1 Set the MN Mode.* page 21
2 Set the Associated Node Number field. page 21
3 Program input categories and priorities. page 21, page 22
4 Create and program an MN Active Tone. page 25
5 Create and program a Fire Active Tone (when Fire is the highest priority). page 29
*MN paging levels are not installed when the DVC acts as a subsidiary device.