Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 21
Programming Programming
NFS2-640/NFS-320/SYS
This field allows the programmer to define the panel’s fire and MN
priority.
On the VeriFire Tools General Settings branch for NFS2-640 or NFS-
320/SYS, select the appropriate setting from the pull-down menu for
the “Mass Notification Priority” field.
Settings:
• Mass Notification not used (Default)
• Mass Notification is a higher priority than fire
• Fire is a higher priority than Mass Notification
DVC
Set the Mode and Paging Level
On the VeriFire Tools General Settings branch for DVC,
select ACU, LOC, CCS, or Subsidiary from the MN
Mode pull-down menu in the DVC MN Mode box.
A DVC that is not an ACU, LOC or CCS on an MN net-
work must be programmed as Subsidiary, and its Associ-
ated Node Number must be 0 (zero).
Select the Paging Levels to enable the ALL CALL but-
tons in the second column of the DVC-KD.
Set the Input Category
Following are the Programmable Audio Matrix (PAM)
Input Numbers, Default Priorities and Categories that
appear for a DVC when ACU, LOC, CCS, or Subsidiary
is selected as the DVC MN Mode. The default priorities
for the first 12 inputs comply with the priorities specified
in UL2572 in that at each level ACU is the highest prior-
ity and CCS is the lowest.
DVC-KD Level buttons in the second column page as
follows:
• Top button (Level 1) - always pages Inputs 1, 3, or
5, depending on whether the DVC is an ACU, LOC
or CCS.
• Second button (Level 2) - always pages Inputs 7, 9, or 11, depending on whether the DVC is an ACU, LOC or CCS.
• Third button (Level 3) - always pages Input 13.
Input Categories are Fire, MN, General, and MN Active Tone:
• When ACU, LOC, CCS, or Subsidiary is selected as a mode, Level 1 inputs default to the MN category, and Level 2 inputs default
to the Fire category.
• “MN Active Tone” is a category (it is assigned to a sequence, there is no default), and it must be assigned only to the MN Active
Tone message sequence (See pages 25–28).
Figure 3.8 Priority Setting - VeriFire Tools,
NFS2-640/NFS-320/SYS
Mass Notification Priority Field
NFS2-640/NFS-320/SYS General Settings Branch,
“General Settings 2” column
Input Number Input Source Default Priority Category
1 ACU Local Paging Level 1 1 MN
2 ACU Network Paging Level 1 2 MN
3 LOC Local Paging Level 1 3 MN
4 LOC Network Paging Level 1 4 MN
5 CCS Local Paging Level 1 5 MN
6 CCS Network Paging Level 1 6 MN
Table 3.1 Default Input Priorities, MN Mode Selected
Figure 3.9 Setting DVC MN Mode & Paging Level
DVC MN
Mode Field
Select the
paging levels
to be used on
the DVC-KD.