EasyManua.ls Logo

Honeywell Notifier DVC User Manual

Honeywell Notifier DVC
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background image
20 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019
Programming Programming
Panel: Navigate through the Panel Settings menu, pressing the
“More” softkey until “MN PRIORITY OVER FIRE” appears.
Press the softkey next to this selection until the appropriate
setting appears, then press “ACCEPT”.
Settings:
YES: MN is the highest priority.
NO: Fire is the highest priority.
MNS NOT USED: The system is for fire protection only.
(Default)
VeriFire Tools: On the VeriFire Tools General Settings
branch for NFS2-3030/NCA-2, select the appropriate setting
from the pull-down menu for the “Mass Notification Priority”
field.
Settings:
Mass Notification not used (Default)
Mass Notification is a higher priority than Fire
Fire is a higher priority than Mass Notification
PANEL SETTINGS
SILENCEABLE WATERFLOW: YES
MN PRIORITY OVER FIRE: YES
SOUNDER BASE STANDBY POWER MON:OFF
ACCEPT
BACK
Figure 3.6 Priority Setting - Panel
Figure 3.7 Priority Setting - VeriFire Tools, NFS2-
3030/NCA-2
NCA-2 General Settings Branch, “General
Settings 2” column
NFS2-3030 General Settings Branch, “General
Settings 3” column
Mass
Notification
Priority Field
Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier DVC and is the answer not in the manual?

Honeywell Notifier DVC Specifications

General IconGeneral
TypeDigital Voice Command
Operating Temperature32°F to 120°F (0°C to 49°C)
CompatibilityNotifier Fire Alarm Control Panels
Operating Voltage24 VDC nominal
Current DrawStandby: 120 mA, Alarm: 250 mA
Humidity Range10% to 93% non-condensing
LED IndicatorsPower
Relay Contacts2 Form C relays
CertificationsFM, CSFM, MEA

Summary

Section 2: Configurations

2.1 Autonomous Control Unit (ACU)

Describes the primary local control unit for a mass notification system.

2.2 Local Operating Console (LOC)

Details the console used by authorized personnel to initiate messages and signaling.

2.3 Central Control Station (CCS)

Explains the system component for emergency communication and control.

Section 3: Programming

3.3.2 Mass Notification Control Settings for the DVC

Explains how to configure MN control settings on the DVC.

3.3.3 Set the Priority

Guides on setting the priority between fire and mass notification events.

3.3.4 MN Mapping

Defines how MN mapping determines fire suppression based on MN alarm status.

Section 4: Operation

4.1 Mass Notification Events

Details how MN events signal locally and over the network.

4.2 Performing a System Reset

Explains the procedure for resetting the system with fire and MN events present.

4.3 Output Event Suppression

Lists factors for achieving desired event suppression in MN systems.

Related product manuals