PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021 15
NEC Power-limited (Class 2) Wiring Requirements Installation
2.4 NEC Power-limited (Class 2) Wiring Requirements
Power-limited (Class 2) and non-power-limited circuit wiring must remain separated in the cabinet. All power-limited (Class 2) circuit
wiring must remain at least 0.25” away from any non-power-limited circuit wiring and all power-limited (Class 2) circuit wiring and
non-power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
Any conduit knockouts may be used. For power-limited (Class 2) applications, use of conduit is optional.
NO NC C NO NC C
TB4
TB15
T
B
2
T
B
1
T
B
1
3
T
B
1
2
T
B
1
1
T
B
1
0
T
B
9
T
B
8
NO NC C
T
B
3
NAC1
AUX1
NAC2
AUX2
Figure 2.6 Power-limited (Class 2) Wiring Example
AC Power
Non-power-limited
Output Circuits
Power-limited Circuits (Class 2)
Relay Contacts
Non-power-limited Circuit
Input Circuits
Power-limited Circuit
(Class 2)
SLC
Power-limited Circuits
(Class 2)
*If the SLC device
does not match the
one in this figure,
refer to the SLC man-
ual wiring conver-
sion charts for legacy
and newer versions of
the modules.
maintain minimum
0.25” between power-
limited and non-power-
limited wiring
Ground fault relay
only available on
Canadian models
Battery
Non-power-limited Circuit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER PSE-6 and is the answer not in the manual?

Honeywell NOTIFIER PSE-6 Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER PSE-6
CategoryExtender
LanguageEnglish

Related product manuals