PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021 9
Open/Short/Ground Fault Trip Values in Standby System Overview
Primary AC Power - TB4
PSE-6(C): 120 VAC, 50/60 Hz, 5.0 amps maximum
PSE-10(C): 120 VAC, 50/60 Hz, 6.2 amps maximum
PSE-6E: 240 VAC, 50/60 Hz, 2.7 amps maximum
PSE-10E: 240 VAC, 50/60 Hz, 3.5 amps maximum
Wire size: #12-14 AWG wire with 600V insulation
Command Input Circuits - TB5, TB6, TB7
Trigger Input Voltage: 9 - 32 VDC
Input Current Draw in Alarm Polarity: 9 - 32 volts, 14.0 mA maximum per input
Output Circuits - TB8-TB14
Supervised and power-limited
Voltage Rating: 24 VDC filtered
Current:
PSE-6: TB8-TB9 – 1A Regulated, 3A special applications; TB10-TB12 – 0.3A Regulated, 3A special applications
PSE-10: TB8-TB11 – 1.5A Regulated, 3A special applications; TB12-TB14 – 0.3A Regulated, 3A special applications
Maximum total alarm current for all output:
PSE-6 - 6.0 amps
PSE-10 - 10.0 amps
Output Circuit Types:
Class B NACs (require 2kΩ - 27kΩ End-of-Line Resistors) and/or Class A NACs using the optional ZNAC-PS Class A
converter module. Use Listed ELRs supplied by the FACP or compatible equipment manufacturer.
Resettable or non-resettable outputs for 24 VDC power outputs or Class D door holder (max ripple voltage: 780mV
RMS
)
Refer to the Notifier Device Compatibility Document #15378 for listed compatible devices.
For wiring requirements, refer to “Wire Requirements” on page 36.
Trouble, AC Loss, and Ground Fault (Canadian models only) Relay Contact Rating - TB1-TB3
Fail-safe Form-C relay (normally energized, transfers with loss of power) for AC Loss and Trouble
4.0 amps @ 30 VDC resistive
Secondary Power (battery) Charging Circuit - TB15
Supervised, non-power-limited
Supports lead acid type batteries only
Float Charge Voltage: 27.6 VDC
Maximum Peak Charge Current: 2.47A
Maximum Nominal Charge Current: 1.5 A
Maximum Battery Capacity: 33.0 AH (with onboard battery charger)
Minimum Battery Capacity: 7.0 AH
1.4 Open/Short/Ground Fault Trip Values in Standby
Table 1.1 lists the earth fault resistance detection in standby for each applicable terminal on the FACP.
Value of the resistance in between any circuit terminal to Earth, which will cause the Ground Fault detection, depends on the ELR cho-
sen for inputs and output circuits. This resistance will vary from 9.9K down to 0 Ohm.
Table 1.2 lists the open/short trip values and restoral values in standby for the NAC circuits on the FACP.
NOTE: The PSE only supports 7AH or 18AH batteries in the cabinet. Other battery capacities up to 33AH will not fit in the cabinet due to
physical dimensions and require a separate battery cabinet.
Output Circuit Terminal Trip Resistance (in ohms)
NAC 1-5/7 + 9.9K or lower
NAC 1-5/7 - 9.2K or lower
ZNAC-PS 1-5/7 + 9.9K or lower
ZNAC-PS 1-5/7 - 9K or lower
Table 1.1 Earth Fault Trip Values
Circuit Fault Trip Resistance (in ohms) Restore Value
NAC 1-5/7 Short 1.6K or lower 1.7K or higher
NAC 1-5/7 Open 55K or higher 33K or lower
ZNAC-PS 1-5/7 Short 1.6K or lower 1.7K or higher
ZNAC-PS 1-5/7 Open 45K or higher 21K or lower
Table 1.2 NAC Open/Short Trip Values

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER PSE-6 and is the answer not in the manual?

Honeywell NOTIFIER PSE-6 Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER PSE-6
CategoryExtender
LanguageEnglish

Related product manuals