EasyManuals Logo
Home>Honeywell>Controller>Sieger System 57

Honeywell Sieger System 57 User Manual

Honeywell Sieger System 57
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
System 57 Quick Start Guide 05701-M-5026 MAN0839 Issue 1
7 Interface Card Connections
System 57 interface cards use a common card with differing numbers of terminal blocks
fitted according to which type of card it is. The picture below illustrates a card with the
maximum number of terminals fitted. The tables show the terminal connections for 5701,
5704 gas and 5704 fire interface cards.
1Fault NC 2Fault NO
3 Fault COM 4 Inhibit COM
5 Inhibit NC 6 Inhibit NO
7 A1(1) NC 8 A1(1) NO
9 A1(1) COM 10 A2(1) COM
11 A2(1) NC 12 A2(1) NO
13 A3(1) NC 14 A3(1) NO
15 A3(1) COM 16 A1(2) COM
17 A1(2) NC 18 A1(2) NO
19 A2(2) NC 20 A2(2) NO
21 A2(2) COM 22 A3(2) COM
23 A3(2) NC 24 A3(2) NO
25 Ground 26 Ground
27 Sensor S 28 Sensor 01
29 Sensor NS 30 Not Connected
31 Analogue O/P(+) 32 Analogue O/P (-)
33 Remote Inhibit In 34 Remote Reset In
35 +24V (Out/In) 36 0V (Out/In)
1 Relay 1 NC 2 Relay 1 NO 1 Relay 5 NC 2 Relay 5 NO
3 Relay 1 COM 4 Relay 2 COM 3 Relay 5 COM 4 Relay 6 COM
5 Relay 2 NC 6 Relay 2 NO 5 Relay 6 NC 6 Relay 6 NO
7 Relay 3 NC 8 Relay 3 NO 7 Relay 7 NC 8 Relay 7 NO
9 Relay 3 COM 10 Relay 4 COM 9 Relay 7 COM 10 Relay 8 COM
11 Relay 4 NC 12 Relay 4 NO 11 Relay 8 NC 12 Relay 8 NO
13 Ground 14 Ground 13 Relay 9 NC 14 Relay 9 NO
15 Channel 1 (S) 16 Channel 2 (S) 15 Relay 9 COM 16 Relay 10 COM
17 Channel 1 (01) 18 Channel 2 (01) 17 Relay 10 NC 18 Relay 10 NO
19 Channel 1 (NS) 20 Channel 2 (NS) 19 Relay 11 NC 20 Relay 11 NO
21 Channel 3 (S) 22 Channel 4 (S) 21 Relay 11 COM 22 Relay 12 COM
23 Channel 3 (01) 24 Channel 4 (01) 23 Relay 12 NC 24 Relay 12 NO
25 Channel 3 (NS) 26 Channel 4 (NS) 25 Relay 13 NO 26 Relay 13 COM
27 Analogue 24V 28 Analogue 0V 27 Relay 14 NO 28 Relay 14 COM
29 Analogue CH1 30 Analogue CH2 29 Relay 15 NO 30 Relay 15 COM
31 Analogue CH3 32 Analogue CH4 31 Relay 16 NO 32 Relay 16 COM
33 Remote Reset 34 Remote Inhibit 33 Ground 34 Ground
35 +24V (In) 36 0V (In) 35 Not Used 36 Not Used
1 Relay 1 NC 2 Relay 1 NO 1 Relay 5 NC 2 Relay 5 NO
3 Relay 1 COM 4 Relay 2 COM 3 Relay 5 COM 4 Relay 6 COM
5 Relay 2 NC 6 Relay 2 NO 5 Relay 6 NC 6 Relay 6 NO
7 Relay 3 NC 8 Relay 3 NO 7 Relay 7 NC 8 Relay 7 NO
9 Relay 3 COM 10 Relay 4 COM 9 Relay 7 COM 10 Relay 8 COM
11 Relay 4 NC 12 Relay 4 NO 11 Relay 8 NC 12 Relay 8 NO
13 Relay 5 NC 14 Relay 5 NO 13 Relay 9 NC 14 Relay 9 NO
15 Relay 5 COM 16 Relay 6 COM 15 Relay 9 COM 16 Relay 10 COM
17 Relay 6 NC 18 Relay 6 NO 17 Relay 10 NC 18 Relay 10 NO
19 Ground 20 Ground 19 Relay 11 NC 20 Relay 11 NO
21 Input CH1 (+) 22 Input CH2 (+) 21 Relay 11 COM 22 Relay 12 COM
23 Input CH1 (-) 24 Input CH2 (-) 23 Relay 12 NC 24 Relay 12 NO
25 Output CH1 (+) 26 Output CH1 (-) 25 Relay 13 NO 26 Relay 13 COM
27 Input CH3 (+) 28 Input CH4 (+) 27 Relay 14 NO 28 Relay 14 COM
29 Input CH3 (-) 30 Input CH4 (-) 29 Relay 15 NO 30 Relay 15 COM
31 Output CH2 (+) 32 Output CH2 (-) 31 Relay 16 NO 32 Relay 16 COM
33 Remote Input (+) 34 Remote Input (-) 33 Ground 34 Ground
35 +24V (Out/In) 36 0V (Out/In) 35 Not Used 36 Not Used
5704 Fire
Hex Relay Card Terminals Relay Interface Card Terminals
5701 Gas
Quad Relay Card Terminals Expansion Relay Card Terminals
5704 Gas
Interface Relay Card Terminals