FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
Blinking at
super short
intervals
A network is set up, and node
access is allowed (the indicator
blinks at 10 Hz, on for 0.05s and
then off for 0.05s).
Table 3-40 describes the indicators on the PSU.
Table 3-40 Indicators on the PSU
The converter has a power input.
The converter has no power input or
is faulty.
Blinking at
long intervals
The converter is being queried (the
indicator blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at
short intervals
The converter application program
is being loaded (the indicator blinks
at 4 Hz, on for 0.125s and then off
for 0.125s).
The converter generates a
forewarning indicating that power
will be limited due to ambient
overtemperature, or generates a
protection shutdown alarm due to
ambient overtemperature or
undertemperature.
Power input overvoltage or
undervoltage protection
Reverse DC input connection
The converter generates no
protection alarms.
Blinking at
long intervals
The communication between the
converter and the outside is
interrupted (the indicator blinks at
0.5 Hz, on for 1s and then off for
1s).