3-6
SETUP
Operator Manual
POWER CORD PLUGS
All 208/240/480V power supplies are shipped with a single-phase power cord and plug. To operate
as a three-phase unit, the user must obtain a power cord and plug that is certified by national or local
electrical codes. The plug should be connected to the power cord by a licensed electrician.
All 200/230/400V and 400V CE power supplies are shipped with a three-phase power cord and no
plug. The user must obtain a plug that is certified by national or local electrical codes. The plug should
be connected to the power cord by a licensed electrician.
POWER CORDS
If the power cord needs to be changed, use the tables below to choose the proper wire size for the
appropriate length cord. Note that the input current used to determine the cord size is I
1eff
. In the U.S.,
use a 3-conductor SO type cord for single-phase, and a 4-conductor SO type cord for three-phase power
supplies. In other countries, use cords that are certified by national or local codes. Prepare the power
cord wires as shown in Fig. 3-6 for non-CE power supplies, or Fig. 3-6a for CE power supplies. Note that
all 4 wires must loop through the toroid in the CE power supply. Cap or tin the conductor leads and use a
#10 terminal on the ground wire. The cord should be installed only by a licensed electrician.
208/240/480/600V Power Supplies
Input Phase Input Recommended Power Cord Gauge Size (AWG)
Voltage Current (I
1eff
) < 10 ft 10 – 25 ft 25 – 50 ft 50 – 100 ft 100 – 150 ft
208 VAC 1 39A 8 8 6 4 4
240 VAC 1 33A 8 8 8 6 4
480 VAC 1 19A 12 12 12 10 8
208 VAC 3 23A 8 8 8 6 4
240 VAC 3 20A 10 10 10 8 6
480 VAC 3 10A 12 12 12 12 10
600 VAC 3 8A 12 12 12 12 10
Input Phase Input Recommended Power Cord Gauge Size (mm
2
)
Voltage Current (I
1eff
) < 3 m 3 – 7.5 m 7.5 – 15 m 15 – 30 m 30 – 45 m
200 VAC 1 40A 10 10 16 25 25
230 VAC 1 35A 6 6 10 16 25
400 VAC 1 23A 4 4 4 6 10
200 VAC 3 23A 4 4 6 16 25
230 VAC 3 21A 2.5 4 6 10 16
400 VAC 3 13A 2.5 2.5 2.5 4 6
200/230/400V Power Supplies
4.5" (114 mm)
3.5" (89 mm)
Figure 3-6 Power Cord Preparation - Non-CE
L1
L2
L3
Ground
#10
Figure 3-6a Power Cord Preparation - CE
4.75" (120 mm)
3.75" (95 mm)
L1
L3
#10
L2
0.5" (13 mm)
Ground
All wires 1 turn
through toroid.

Table of Contents

Other manuals for Hypertherm powermax900

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hypertherm powermax900 and is the answer not in the manual?

Hypertherm powermax900 Specifications

General IconGeneral
BrandHypertherm
Modelpowermax900
CategoryWelding System
LanguageEnglish

Related product manuals