INSTALLATION AND OPERATION INSTRUCTIONS
3-4
SFC BOILER / WATER HEATERS - SFC 199
INSTALLATION AND OPERATION INSTRUCTIONS
3-4
SFC BOILER / WATER HEATERS - SFC 199
3.4 FUEL CONVERSION
The SFC series modulating unit is factory re-tested to operate with natural gas.
The rating plate is marked to indicate which fuel the particular unit has been set
up with. Firing a unit with a fuel other than what is listed on the rating plate is
prohibited unless the following conversion procedure is completed by a qualied
technician.
Fuel conversion requires hardware adjustments (orice replacement) as well as
measurement and possible tuning of the low re mixture. Detailed instructions
including parts and labeling are found in Fuel Conversion kits. Refer to Table 11
for the correct kit number.
NATURAL GAS PROPANE
CO
2
VALUE (%) AT HIGH FIRE WITH THE FRONT COVER OPEN
Max. CO
2
value 10.1% 11.5%
Min. CO
2
value 9.1% 9.8%
CO
2
VALUE (%) AT LOW FIRE WITH THE FRONT COVER OPEN
Max. CO
2
value = Actual value at High re
= Actual value at High re
– 0.3%
Min. CO
2
value 9.1% 9.5%
Table 12: CO
2
Values and High and Low Fire
The following procedure must be carried out by a qualied technician.
1. Ensure that the gas supply is turned off at the manual gas valve.
2. Disconnect the electrical power.
3. Disconnect the nut at the gas valve outlet (top of the gas valve) and remove
the orice and O-ring.
4. Insert the correct orice into the O-ring, and re-install into the nut at the gas
valve outlet (top of the gas valve) and then tighten the nut.
5. Restore the gas supply by opening the manual gas valve.
6. Test for leaks by using an approved leak detection solution on all joints.
7. Carefully follow the “Prior to Start-Up” – Section 3.2 and “Commissioning” –
Section 3.3 procedures on the preceeding pages 3-2 and 3-3.
DANGER
Operating any IBC unit using
a fuel other than the fuel
listed on its rating plate is
prohibited. If the information
in this section related to
conversion to alternative
fuels is not followed exactly,
a dangerous situation can
result, leading to re or
explosion, which may cause
property damage, personal
injury, or loss of life.
Figure 42: Orice and O-ring
PROPANE ORIFICE CHART
MODEL
NUMBER
ORIFICE
SIZE
SFC 199 535
NATURAL GAS ORIFICE
CHART
MODEL
NUMBER
ORIFICE
SIZE
SFC 199 660
ALTERNATIVE
NATURAL GAS ORIFICES
FOR CALORIFIC VALUES
750–900 BTU/FT
3
MODEL
NUMBER
ORIFICE
SIZE
SFC 199 725

Table of Contents

Other manuals for IBC SFC-199

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBC SFC-199 and is the answer not in the manual?

IBC SFC-199 Specifications

General IconGeneral
BrandIBC
ModelSFC-199
CategoryIndustrial Equipment
LanguageEnglish