15
IDS 805 Installer Manual 700-266-02H Issued September 2009
12.4 Program Location Summary
Following is a detailed description of the functioning of each location and its options.
LOCATION 0 Defaulting of the Panel or Master User Code
0 Resets all locations to the factory default values as shown in the DEFAULT
column in the programming list. All user codes will also be defaulted and the
master code will become 1234.
Will default the master user code to 1234 without defaulting the remainder of
the user codes. All other information will remain unaltered.
2 Will reset all reporting codes to 0. If a communicator format other than Contact
ID is used, the reporting codes need to be reprogrammed. It is advisable to
default all reporting codes to 0 prior to reprogramming the codes.
LOCATIONS 1-8 Zone Characteristics (Zones 1-8)
Program locations 1 to 8 define the zone characteristics of each of the eight zones. Each zone can be
programmed to function in one of eleven modes. Table 4 provides a location/zone cross-reference
together with the default zone characteristics.
Table 4: Location/Zone Defaults
1 1 1 Entry/Exit
2 2 2 Follower
3 3 4 Audible Instant
4 4 4
Audible Instant
5 5 4
Audible Instant
6 6 4
7 7 4
Audible Instant
8 8 3 Audible Priority
Table 5 overleaf provides a description of the different zone types that may be programmed into these
locations i.e. a value of 3 programmed into location 5 would cause zone 5 to be an audible priority zone.