Page: 12
FM-200® FILL MANUAL
Revision B
Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Section 3 Fill Components
3.4 Valve Closing Adapter
P/N 17292 (See Figure 3.4)
e valve closing adapter is threaded onto the valve actuation connection of
the cylinder valve and receives pressure from the nitrogen supply at the end of
the lling procedure to close the cylinder valve. A 1/4 inch (8 mm) male quick-
connect tting (P/N 99499) is installed in the 1/4 inch (8 mm) FNPT inlet
port of the valve closing adapter and is utilized to facilitate connection to the
valve closing line of the nitrogen regulator-hose assembly.
3.5 Agent Supply Tank
FM-200® agent is supplied in tanks of 160 lb (73 kg), 1200 lb (544 kg), and 34,000 lb (15,422 kg) capacities.
Each supply tank has a valve marked as the vapor ll line and a valve marked as the liquid ll line. e liquid
ll line shall be utilized in lling a cylinder assembly.
3.6 Agent Fill Station
P/N 99502 (See Figure 3.6)
e agent ll station is necessary to pump the liquid agent from the agent supply tank into the empty
cylinder assembly. e station pump requires a dry compressed air supply capable of pressure between 100
and 120 psi (6.89 and 8.27 bar) at a minimum of 13 cubic feet per minute.
e agent ll station has an inlet hose (agent supply tank hose) designed to connect to the agent supply tank
and an outlet hose (cylinder ll hose) designed to connect to the cylinder ll assembly.
1/4" (8 mm)
Male Quick-Connect
Fitting (P/N 99499)
Figure 3.4 Valve Closing Adapter
Figure 3.6 Agent Fill Station
Selector
Control
Knob
Liquid/
Moisture
Indicator
Discharge
Pressure
Gauge
Inlet Pressure Gauge
Pump Control
Knob
Agent/Nitrogen
Selection Knob