FM-200® FILL MANUAL
Revision B
Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Section 4 Fill Procedure
4.3.1 Finalization Procedure
Upon reaching an internal cylinder assembly pressure of 360 psig at 70°F (refer to Table B.1 located in
Appendix B for intended cylinder pressures adjusted for ambient temperatures other than 70°F), the
following steps shall be performed.
• Let the cylinder assembly stand for three hours. Once this three hour period has been completed, check
the cylinder assembly for leak using a soap solution.
• Check the cylinder pressure gauge using the pressure/temperature chart located in the appendix of this
manual.
• Weigh cylinder assembly and record this nal weight on the cylinder label and ll log as full weight.
• Properly secure the cylinder assembly for storage or shipping.