FM-200® FILL MANUAL
Revision B
Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Section 4 Fill Procedure
• Remove the valve closing adapter from the cylinder valve.
• Remove the cylinder ll hose from the pump connection port. If the cylinder ll hose quick-connect
tting is dicult to remove, this indicates the cylinder ll hose is still under pressure. Repeat the above
steps to depressurize the cylinder ll hose.
• Disconnect the cylinder ll assembly from the ll adapter.
• Remove the ll adapter and immediately install the anti-recoil safety device into the cylinder discharge
outlet.
• Observe the weight displayed on the scale. Subtract from this weight the previously recorded empty
cylinder weight to determine the actual weight of the agent currently stored within the cylinder. e
actual weight of the agent should equal the intended ll weight. If the actual weight of the agent is
less than the intended ll weight, the agent ll procedure must be repeated. If the actual weight of the
agent is more than the intended ll weight, the overll retrieval procedure must be followed as detailed
below.
• If the intended agent ll weight has been achieved, record the agent weight in the appropriate location on
the cylinder label and ll log. Follow the steps outlined in Section 4.3 to superpressurize the cylinder.
4.2.3 OverllRetrievalProcedure
To retrieve agent from a cylinder assembly due to an overll, it will be necessary to open the cylinder valve.
Both a manual and electric valve actuator will be required for this purpose.
• Replace the anti-recoil safety device with the appropriate Series ll adapter for the cylinder assembly
being lled.
• Ensure that the ll pressure gauge is connected to the gauge connection port of the cylinder ll
assembly.
• Connect the cylinder connection port of the cylinder ll assembly to the male quick-connect tting of
the ll adapter. Ensure the manual agent ll valve of the cylinder ll assembly is in the closed position
before proceeding.
• Ensure that the agent supply tank hose of the ll station is connected to the liquid ll line of the agent
supply tank.
• Connect the cylinder ll hose of the ll station to the pump connection port of the cylinder ll
assembly.
• Open the supply tank liquid line valve.
• Set the direction of ow for the ll station towards the agent supply tank. Do this by setting the pump
selector knob to "recovery cylinder".
• Open the manual agent ll valve and set the ll station pump to a low speed using the pump control
knob.