FM-200® FILL MANUAL
Revision B
Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
e face of the agent ll station contains three displays (liquid/moisture indicator, inlet pressure gauge,
discharge pressure gauge) and three controls (selector control knob, pump control knob, agent/nitrogen
selection knob). ese displays and controls are described below. Refer to the manual provided with the
agent ll station for more information on any of these features.
3.6.1 Fill Station Displays
e liquid/moisture indicator is used to verify a liquid agent ow through the ll station pump. e inlet
pressure gauge displays the pressure on the agent supply tank side of the ll station pump. e discharge
pressure gauge displays the pressure on the cylinder ll side of the ll station pump.
3.6.2 Selector Control Knob
e selector control knob changes the direction of ow for the ll station. Setting this knob to "systems
cylinder" directs the ow toward the cylinder ll hose. Setting the knob to "recovery cylinder" directs
the ow toward the agent supply tank hose. Setting the selector control knob to "o" places the pump
in a neutral position, stopping the ow to either direction. e selector control knob shall be set to "o"
whenever connecting or disconnecting the agent supply tank hose or cylinder ll hose.
3.6.3 Pump Control Knob
e pump control knob is utilized to adjust the speed of the ll station pump. Turning the knob clockwise
increases the speed and turning the knob counterclockwise decreases the speed. e pump control knob
shall be set to "o" whenever connecting or disconnecting the agent supply tank hose or cylinder ll hose.
3.6.4 Agent/Nitrogen Selection Knob
e agent/nitrogen selection knob changes the ll station pump from agent ll mode to nitrogen ll mode.
e recommended ll procedure as detailed in this manual does not utilize the agent ll station for nitrogen
therefore the agent/nitrogen selection knob should remain set to "liquid HFC-227" throughout the course
of the ll procedure.
Section 3 Fill Components