KNX Room actuator 230 V
Ref.-no.: RA 23024 REGHE
L After failure and return of mains voltage, the device switches over to bus
operation.
L Manual control mode can be disabled in operation via bus telegram.
4.4 Blind/shutter control priorities
• Highest priority: manual control
• 2nd priority: forced-control position
• 3rd priority: safety function
• 4th priority: sun protection
• Lowest priority: bus operation: raising / lowering, slat adjustment,
scenes, positioning
Activating the temporary manual control mode
Keypad operation must have been programmed beforehand
and not be disabled.
• Press the
key briefly, < 1 s,
LED A1 flashing, LED remains off.
L After 5 s without key-press, the actuator returns automatically to the bus
mode.
Deactivating the temporary manual control mode
The device must be in the temporary manual control mode.
• No key-press for 5 s.
- or -
• Press the
key briefly, < 1 s, several times until the desired output
status.
LEDs A1...A6 are no longer flashing, but indicating the output status.
Switching outputs: Depending on programming, the output relays switch
over to the position active at the time of deactivation of the manual
control mode, e.g. to forcing and logic operation.
Shutter outputs: Depending on programming, the blinds/shutters move to
the position active at the time of deactivation of the manual control
mode, e.g. forced-control position, safety or sun protection position.
Heating outputs: Depending on programming, the outputs switch over to
the position active at the time of deactivation of the manual control
mode, e.g. to forcing and logic operation.
Activating the permanent manual control mode
Keypad operation must have been programmed beforehand and not be
disabled.
• Press the
key for at least 5 s.
LED is on , LEDs A1 is flashing, the permanent manual control mode
is activated.
Deactivating the permanent manual control mode.
The device is in the permanent manual control mode.
• Press the
key for at least 5 s.
The
LED is off, bus operation is activated.
Switching outputs: Depending on programming, the output relays switch
5