KNX Room actuator 230 V
Ref.-no.: RA 23024 REGHE
Fig. 5: Connection of blind/shutter motors
Observe the permissible load ratings (Technical data).
The output must have been parameterized as switching output.
Caution!
Risk of irreparable damage if several drives are connected in parallel
to one output.
Limit switch contacts can weld together and drives, blinds/shutters
and the shutter actuator can be irreparably damaged. Use an isolating
relay.
• Connect the drives (Fig 5).
5.5 Connecting 230 V valve drives
Fig. 6: Connection of electro-thermal
230 V valve drives
• Connect the valve drives (Fig. 6). Connect 4 valve drives maximum to
one output.
L Connect only electro-thermal valve drives.
L In the case of electro-thermal valve drives, attention must be paid to the
working characteristics normally open or normally closed (see project
design data).
5.6 Attaching the bus terminal cap
Connecting terminal for bus line to insert
Fig. 7: Protective cap
9