KNX Room actuator 230 V
Ref.-no.: RA 23024 REGHE
10
To protect the bus line against dangerous voltages at the connecting
terminal, slide on the protective cap.
• Lead bus lines towards the rear of the device.
• Snap the cap onto the bus terminal (Fig. 7, A).
Removing the bus terminal cap
• Press the sides and pull out the cap (Fig. 7, B).
6 Start-up
6.1 Measuring the blind/shutter and slat running times
The blind/shutter running time is important for positioning
and scene moves. With Venetian blinds, the slat adjusting time is - for
technical reasons - part of the overall running time of blinds/shutters. The
opening angle of the slats is therefore defined as the running time required
between the ‚open‘ and ‚closed‘ positions.
The upward move is generally longer than the downward move and is
accounted for as running time prolongation in percent.
• Measure the UP and DOWN running times of the blind/shutter.
• Measure the slat adjusting time.
• Enter the measured values into the parameter settings list.
6.2 Loading the physical address and the application
software
• Switch on the bus voltage.
• Assign a physical address and download the application software (with
commissioning software).
• Switch on the mains voltage at the outputs.
Appendix
7 Technical data
KNX-medium TP1
Commissioning mode S-mode
KNX supply 21...32 V DC
KNX power consumption max. 150 mW
Rated voltage AC 230 / 240 V~
Mains frequency 50/60 Hz
Heat dissipation max. 6 W
Ambient temperature -5 °C...+45 °C
Storage temperature -25 °C...+70 °C
Fitting width 72 mm (4 TE)
Weight approx. 290 g
Connection
KNX connecting terminal
230 V supply and outputs screw terminals