KP310V1.0 Controller Operation Manual
- 16 -
If there is no operation for more than 60s, system will automatically exit Parameter Set menu, and
enter the System Operation menu.
8.1 Parameters Set list
V
A
R
Model KP310V1.0
V
O
RUN
V
A
R
Model KP310V1.0
V
O
RUN
No. Parameters Code Range Accuracy Defaults Description
Engine
1 Flywheel Gears ○○○○○● 1-500 1 100
2 Tripping speed ○○○○●○ 0-3000 1rpm 600
Engine RPM when starter is
tripping
3
Tripping
frequency
○○○○●● 0-600 0.1Hz 200
Genset Frequency when starter is
tripping
4
Tripping
charging voltage
○○○●○○ 0-400 0.1V 50
Charging alternator voltage when
starter is tripping
5 Starting timer ○○○●○● 1-100 0.1s 5 Genset start timer
6
Tripping oil
pressure delay
○○○●●○ 1-100 0.1s 5
Oil pressure when starter is tripper
7
Maximum
starting time
○○○●●● 1-100 0.1s 30
Average starter working Time
8 Under RPM ○○●○○○ 0-6000 1rpm 0 Engine under speed
9 Over RPM ○○●○○● 0-6000 1rpm 1600 Engine over speed
10
Under RPM
fault delay
○○●○●○ 0-65535 0.1s 0
Engine under speed delay
11
Over RPM fault
delay
○○●○●● 0-65535 0.1s 0
Engine over speed delay
12
Engine Stop To
Start Delay
○○●●○○ 10-65535 0.1s 30
Engine Stop to start delay timer
Parameter Code