TP-6694 6/22 103
3.7 Crankcase Ventilation (CCV) Heater Kit GM78171-KP1
Applies to 125/150 kW, 8.1 L GM-powered and 8.8 L PSI-powered generator set models. Consult your local generator set
distributor/dealer for additional information.
The crankcase ventilation (CCV) heater kit provides a controlled heating source to the crankcase ventilation system preventing
freezing water buildup during cold weather. The thermostat turns on at 4°C (40°F) and turns off at 16°C (60°F) reducing energy
consumption. See Figure 48.
Figure 48 Crankcase Ventilation Heater Kit
3.8 Air Cleaner Restriction Indicator (if equipped)
The air cleaner restriction gauge mounted on the air cleaner(s) helps determine the air cleaner change interval.
The air cleaner restriction gauge monitors air flow and continuously displays restriction readings indicated as vacuum
(see Figure 49). Increased restriction indicates a clogged air cleaner element.
As maximum allowable restriction is reached, the gauge window turns red indicating the air cleaner element needs replacement.
To reset the gauge, push the gauge top down and release.
Figure 49 Restriction Indicators (styles vary)