TP-6694 6/22 161
Appendix B. Programmer-Defined Settings
Use the table below to record programmer-defined settings during the generator set controller setup and calibration. The
controller default settings and ranges provide guidelines. The table contains all faults with ranges and time delays including
items that do not have adjustments. Some notices give the programmer a choice to make them active Not adjustable
programmer-defined settings result when the controller logic does not allow changes or the values are engine limited.
SiteTech™ software is required for programming the APM402 controller. Contact your local distributor/dealer for assistance.
Notes:
Inhibit time delay is the time delay period after crank disconnect.
The engine ECM may limit the crank cycle even if the controller is set to a longer time period.
Programmer-Defined Settings
Description
Controller
Display
Message
Write
Access
Display
SiteTech
GenSet
Mode
Always
Running
Stopped
Range
Setting
Default
Selection
Time
Delay
Range
(sec.)
Default
Time
Delay
(sec.)
Programmer-
Defined
Settings
Engine Functions
Critically high fuel level
(diesel-powered models
only) *
Fuel Level
Critically High
0-100%
95%
0-10
5
ECM communications
loss
ECM Comm Err
Shutdwn
Fixed
10
Not adjustable
ECM diagnostics
(multiple inputs)
ECM xxxxxx
Warning
Not adjustable
ECM diagnostics
(multiple inputs)
ECM xxxxxx
Shutdwn
Not adjustable
ECM faults (address
conflict)
ECM Addr Err
Shutdwn
Not adjustable
ECM faults (model
mismatch)
ECM Mismatch
Shutdwn
0-255
0
Engine over speed
Eng Speed
High Shutdwn
S
A
105-120%
115%
Engine RPM (manual
speed adjust) Version
3.10.3 or higher
Engine RPM
Display
DS
A
60 Hz:
1751-1849
50Hz:
1451-1549
60 Hz:
1800
50 Hz:
1500
Engine start aid active
Starting Aid
Notice
Engine under speed
Eng Speed Low
Shutdwn
S
A
75-95%
85%
Fuel tank leak *
Fuel Leak
Warning
Not adjustable
Fuel tank leak *
Fuel Leak
Shutdwn
Not adjustable
High battery voltage
Battery High
Warning
S
A
110-135%
125%
Fixed
10
Not adjustable
High coolant
temperature
Coolnt Temp
High Warning
0-10
(0-30
inhibit)
5 (0
inhibit)
High coolant
temperature
Coolnt Temp
High Shutdwn
0-10
(0-30
inhibit)
5 (0
inhibit)
High fuel level (diesel-
powered models only) *
Fuel Level High
Warning
0-100%
90%
0-10
5
Loss of fuel
Loss of fuel
Not adjustable
Low battery voltage
Battery Low
Warning
S
A
80-105%
100%
Fixed
90
Not adjustable

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler 25CCL and is the answer not in the manual?

Kohler 25CCL Specifications

General IconGeneral
BrandKohler
Model25CCL
CategoryPortable Generator
LanguageEnglish

Related product manuals