84 Section 5 Decision-Makerr 550 Controller TP-6356 4/12
Status or Fault
User-Defined
Settings
Time
Delay
(sec.)
Inhibit
Time
Delay*
(sec.)
Default
SelectionRange Setting
Relay
Driver
Output
(RDO)
Digital
Display
Refer
to
Menu
Idle (speed) Mode Function
Digital Aux. input D21
9, 10 Idle Speed
Active
RDO-21 Fixed inhibit time 0 sec.
inhibit,
60 sec.
delay
0--600
Load Shed
kW Overload
10 Load Shed
KW Over
RDO-30 80%--120% 100% of kW
rating
5
Load Shed Underfrequency 10 Load Shed
Under
Frequency
RDO-31 59, (60 Hz)
49, (50 Hz)
5
Low Battery Voltage 10 Low Battery
Voltage
RDO-12 10--12.5 (12V)
20--25 (24V)
12 (12V)
24 (24V)
10
Low Coolant Level 10 Low Coolant
Level
RDO-14 30 5 Not adjustable
(Low) Oil Pressure
Shutdown
10 Oil Pressure
Shutdown
RDO-04 30 5 Not adjustable
(Low) Oil Pressure Warning 10 Oil Pressure
Warning
RDO-07 30 Not adjustable
No Coolant Temperature
Signal
10 No Cool
Temp Signal
30 Not adjustable
No Oil Pressure Signal 10 No Oil
Pressure
Signal
30 Not adjustable
Overcrank Shutdown 8 Over Crank RDO-02 0 --6 cycles 3 cycles
Overcurrent 10 Over Current 110% 10
Overfrequency Shutdown 7, 10 Over
Frequency
RDO-28 102%--140% 140% std.
103% FAA
10
Overspeed Shutdown 7, 10 Over Speed RDO-01 65--70 (60 Hz)
55--70 (50 Hz)
70 (60 Hz)
60 (50 Hz)
0.25
Overvoltage Shutdown 7, 8,
10
Over Voltage RDO-20 105% --135% 115%
2-sec. time
delay
2--10
Password (access code) 14 0(zero) See Access Code
entry
Time Delay Engine
Cooldown (TDEC)
8, 10 RDO-23 00:00 --10:00
min:sec
5:00
Time Delay Engine Start
(TDES)
8, 10 00:00--5:00
min:sec
00:01
Time Delay Starting Aid 8, 10 0--10 sec.
Underfrequency Shutdown 7, 10 Under
Frequency
RDO-29 80%--95% 90% 10
Undervoltage Shutdown 7, 8,
10
Under
Voltage
RDO-27 70%--95% 85%
10-sec.
time delay
5--30
Weak Battery 10 Weak
Battery
RDO-26 60% of
nominal
2
* Inhibited time delay is the time delay period after crank disconnect.