83Section 5 Decision-Makerr 550 ControllerTP-6356 4/12
5.3.6 User-Defined Settings (Code Version Prior to 2.10)
Use the table below to record user-defined settings
during the generator set controller setup and calibration.
The controller default settings and ranges provide
guidelines. The table contains all faults with ranges and
time delays including items that do not have
adjustments.
Note: The engine ECM may limit the crank cycle even if
the controller is set to a longer time period.
Status or Fault
Refer
to
Menu
Digital
Display
Relay
Driver
Output
(RDO)
Range Setting
Default
Selection
Inhibit
Time
Delay*
(sec.)
Time
Delay
(sec.)
User-Defined
Settings
AC Sensing Loss 10 AC Sensing
Loss
RDO-25 Not adjustable
Access Code (password) 14 0(zero)
Analog Aux. Inputs 1--7 9 User-Defined
A1--A7
Default values with
Warning Enabled:
HI warning 90%,
LO warning 10%,
HI shutdown 100%,
LO shutdown 1%
30 sec.
inhibit, 5
sec. delay
0--60 0--60
Analog Aux. Input 1 9 Coolant
Temperature
Default values with
Warning Enabled:
HI/LO warning and
HI/LO shutdown are
all engine
dependant
30 sec.
inhibit, 0
sec. delay
0--60 0--60
Analog Aux. Input 2 9 Oil Pressure Default values with
Warning Enabled:
HI/LO warning and
HI/LO shutdown are
all engine
dependant (255 psi
max.)
30 sec.
inhibit,
0 sec. delay
warning,
5 sec. delay
shutdown
0--60 0--60
Cyclic Cranking 8 1--6 crank cycles
10--60 sec. crank on
1--60 sec. pause
3 cycles
15 sec.
15 sec.
Defined Common Faults 10 User-Defined RDO-18 Default shutdowns
include:
Emergency stop
High coolant temp
Low oil pressure
Overcrank
Overspeed
30 sec.
inhibit,
5 sec. delay
0--60 0--60
Digital Aux. Inputs 1--21 9 User-Defined
D1--D21
30 sec.
inhibit, 5
sec. delay
0--60 0--60
EPS (Emergency Power
System) Supplying Load
10 EPS
Supplying
Load
RDO-15 5% of rated
line current
High Battery Voltage 10 High Battery
Voltage
RDO-13 14.5--16.5 (12V)
29--33 (24V)
16 (12V)
32 (24V)
10
High Coolant Temperature
Shutdown
10 Hi Cool
Temp
Shutdown
RDO-03 30 5 Not adjustable
High Coolant Temperature
Warning
10 Hi Cool
Temp
Warning
RDO-06 30 Not adjustable
High Oil Temperature
Shutdown
10 Hi Oil Temp
Shutdown
RDO-17 30 5 Not adjustable
* Inhibited time delay is the time delay period after crank disconnect.