86 Section 5 Decision-Makerr 550 Controller TP-6356 4/12
Status Event
or Fault
User-Defined
Settings
Time
Delay
(sec.)
Inhibit
Time
Delay
(sec.)
Default
Selection
Range Setting
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
Analog Aux. Input
A06 VSG (V olvo,
GM, Doosan only)
9, 12 A06
ANALOG
AUXILIARY IN
Volvo:
0.5V=1250
4.5V=8750
GM/Doosan
60 Hz:
0.5V=2375
4.5V=2625
50 Hz:
0.5V=2327
4.5V=2624
—
Analog Aux. Input
A07
9, 11 A07
ANALOG VOL T
ADJUST
±10% of system
voltage over the range
of 0.5--4.5 VDC
Battery Charger Fault
(see D01) **
—
Battle Switch
(Fault Shutdown
Override Switch)
9 BATTLE
SWITCH
Fixed Not adjustable
Block Heater
Control[[
10 BLOCK HEATER
CONTROL
RDO only
Breaker Trip w
10 BREAKER
TRIP
RDO-30 Not adjustable
Common Protective
Relay Output w
10 COMMON PR
OUTPUT
RDO-31 w
Not adjustable
Critical Overvoltage
Shutdown
10 CRITICAL
OVERVOLTAGE
Fixed 275 volts
(L1--L2)
Not adjustable
Cyclic Cranking 8 1--6 crank cycles
10--30 sec. crank on
1--60 sec. pause
3
15 sec.
15 sec.
Defined Common
Faults
(each input value is
set separately)
10 DEFINED
COMMON
FAULT
RDO-18
(lead 32A)
Default shutdowns
include:
Emergency stop
High coolant temp
Low oil pressure
Overcrank
Overspeed
30 sec.
inhibit,
5 sec. delay
0--60 0--60
Detonation Shutdown
(see D13) ]
—
Detonation Warning
(see D12) ]
—
Digital Aux. Input
D01--D21
9, 10 USER-DEFINED
D01--D21
30 sec.
inhibit,
5 sec. delay
0--60 0--60
Digital Aux. Input
D01 Battery Charger
Fault **
9, 10 D01 BATTERY
CHARGER
FAULT
RDO-11
(lead 61)
Fixed 0 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D02 Low Fuel
Warning **
9, 10 D02
LOW FUEL
WARNING
RDO-08
(lead 63)
Fixed 0 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D03 Low Coolant
Temperature **
9, 10 D03 LOW
COOLANT
TEMP
RDO-05
(lead 35)
Fixed 0 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D04 Field
Overvoltage (M4, M5,
or M7 alternator only)
9, 10 D04
FIELD
OVERVOLTAGE
Fixed 1 sec.
inhibit,
15 sec.
delay
Not adjustable
Digital Aux. Input
D05 Breaker
Closed w
9, 10 D05
BREAKER
CLOSED
Fixed 0 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D06 w
9, 10 D06 ENABLE
SYNCH
20 sec.
inhibit,
0 sec. delay
Not adjustable
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC
] Waukesha-powered models ]] FAA only
w Paralleling applications