88 Section 5 Decision-Makerr 550 Controller TP-6356 4/12
Status Event
or Fault
User-Defined
Settings
Time
Delay
(sec.)
Inhibit
Time
Delay
(sec.)
Default
Selection
Range Setting
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
EPS (Emergency
Power System)
Supplying Load
10 EPS
SUPPL YING
LOAD
RDO-22 Fixed 1% of rated
line current
Not adjustable
Field Overvoltage
(see D04)
Not adjustable
Fuel Level (see A04) —
Fuel Valve Relay ]
10 FUEL VALVE
RELAY
RDO-23 ]
Not adjustable
Generator Set
Running
10 RDO-15
(lead 70R)
Not adjustable
Ground Fault
Detected
10 GROUND
FAULT
Not adjustable
High Battery Voltage 10 HIGH
BATTERY
VOL TAGE
RDO-13 14.5--16.5 V (12 V)
29--33 V (24 V)
16 V (12 V)
32 V (24 V)
10
High Coolant
Temperature
Shutdown
10 HI COOL TEMP
SHUTDOWN
RDO-03
(lead 36)
30 5 Not adjustable
High Coolant
Temperature Warning
10 HI COOL TEMP
WARNING
RDO-06
(lead 40)
30 Not adjustable
High Oil Temperature
Shutdown
10 HI OIL TEMP
SHUTDOWN
30 5 Not adjustable
High Oil Temperature
Warning ][[
10 HI OIL TEMP
WARNING
30 Not adjustable
Idle (speed) Mode
Function (see D21)
—
In Synch w
10 IN SYNCH RDO-29 * Not adjustable
Intake Air
Temperature
Shutdown [[
10 INTAKE AIR
TEMP SDWN
30 Not adjustable
Intake Air Temp.
Warning [[
10 INTAKE AIR
TEMP WARN
30 Not adjustable
Intake Air Temp.
Warning(seeA03)]
—
Intake Air Temp.
Shutdown (see
A03)]
—
Internal Fault
Shutdown
10 INTERNAL
FAULT
Not adjustable
J1939 CAN
Shutdown (see
Engine J1939 CAN
Shutdown)
—
Knock Shutdown
(see D13) ]
—
kW Overload
(see Load Shed)
—
Load Shed
kW Overload ]]
10 LOAD SHED
KW OVER
RDO-30 ]]
80%--120% 100% of kW
rating with
5 sec. delay
2--10
Load Shed Over
Temperature [[
(Activated by a High
Coolant Temp.
shutdown)
10 LOAD SHED
OVER
TEMPERATURE
RDO only Not adjustable
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC
] Waukesha-powered models ]] FAA only
w Paralleling applications