2-M7
GL6000, GL7000, GL9000, GL11000, WSM
GENERATOR
4. EARTH
NOTE
To avoid electric shock, connect a grounding
cable to the ground terminal and ground it as
shown in the figure. Use a 3 mm
2
or larger copper
grounding cable whose grounding resistance is
below 10 .
Ground the generator as much as possible.The end
user, equipment owner or operator must contact his
local, state, county or municipal electric code department
to determine the approved generator grounding method
to be used in his application or location.
Recommendations in the NEC, NFPA and OSHA
regulations must be followed to assure compliance and
safe operation.
A grounding lug is provided on the KUBOTA
generator frame for earth grounding depending on local,
state, national or OSHA requirements.
One possible connection method for construction site
use is as follows.
W1018675
(1) Generator Ground Terminal
(2) AWG Flexible Copper Ground
Connection
(3) Metal Ground Rod or Building
Cold Water Pipe System Per
N.E.C. Cord
KiSC issued 05, 2015 A

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kubota GL11000 and is the answer not in the manual?

Kubota GL11000 Specifications

General IconGeneral
ModelGL11000
TypePortable Generator
Fuel TypeDiesel
Fuel Tank Capacity28 liters
Frequency50 Hz
Voltage230 V
Starting SystemElectric Start
PhaseSingle Phase
EngineKubota D722
Noise Level at 7 m72 dBA

Related product manuals