EasyManuals Logo
Home>Lamtec>Control Systems>AEC-TPS

Lamtec AEC-TPS User Manual

Lamtec AEC-TPS
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #85 background imageLoading...
Page #85 background image
84
5 Functional Description with Process Diagrams
5.1.4 Default Process Flow for Oil Modulating Without Pilot Burner
Fig. 5-7 Process sequence chart for oil modulating without pilot burner
Fig. 5-8 Oil train oil modulating without pilot burner
Signal bar Significant times and their parameters Standard
Signal must be present. t4* Parasitic light monitoring time P803 5.0 s
Signal must not be present. t5 Pre-ventilation time P318 1 - 999 s
Signal can be present. t6 Transformer pre-activation time P309 3.0 s
t7 1
st
safety time P305 4.0 s
t11 Control release delay time P380 0.0 s
t13 Post-ventilation time P319 0.0 s
t22 Program monitoring time P304 600 s
t23 Irrelevance time P323 2.0 s
V1 Fuel valve on oil side M Actuator drive for gas damper
V2 Fuel valve on burner side

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec AEC-TPS and is the answer not in the manual?

Lamtec AEC-TPS Specifications

General IconGeneral
BrandLamtec
ModelAEC-TPS
CategoryControl Systems
LanguageEnglish

Related product manuals