28
6 Commissioning
6.1 Operating Conditions
NOTICE
If the LT3 is being used for O
2
control or the LT3-F for CO/O
2
control, it may happen, that the
connected LSB-modules are not be controlled correctly. The LSB modules start to flash red
and the output values are disturbed.
To avoid this, the ETAMATIC or when FMS/VMS then the connected communications proces-
sor board/fieldbus module requires a software update to the latest version.
Please check the version before commissioning.
Function up from software version for communication processor for LSB:
If you have any questions, please contact support@lamtec.de or phone +49 6227 605233.
Shown on the ETAMATIC: Using PC software for remote control view version
„Software Version Communication Processor’“
Software-EPROM on processor board in ETAMATIC
Shown on the FMS/VMS:
or
Check on the label ‘Software’ printed on the outside of the
housing of communications processor board / fieldbus mod-
ule
Using PC software for remote control view version
"Software Version Secondary Communication Processor“
Software-EPROM in communications processor board/field-
bus
When ETAMATIC / ETAMATIC OEM: B9w001, up from April 2015
When communication processor / PROFIBUS connection
for FMS/VMS
A9xxx, up from November
2011
When MODBUS connection RTU for FMS/VMS: M9xxx, up from April 2015
When MODBUS connection TCP for FMS/VMS: E9xxx, up from June 2011