10.5.1 Commissioning of the Additional Modules
Checking the module
• Ensure that the CAN LOW and CAN HIGH, as well as the 24V voltage supply, are con-
nected correctly.
• Make sure that a terminal resistance of 120
is set at the free connecting point between CAN LOW and CAN HIGH.
• Setting the address on the module (tens at the top, ones at the bottom)
– LSB module with 4 analogue outputs: LSB address 19
– LSB module with 4 digital outputs: LSB address 03
– LSB module with 4 digital inputs: LSB address 11 – Modules for calculating the efficiency
or field bus connection do not require
an own LSB address
• With digital modules, the switches of the manual operating levels must be set to "A."
After switching on, you should see the following status
• Red LED off on the LSB module
• Green LED flashes on the LSB module
If not, consider the following problem solutions
• No LED on the LSB module lit
– No 24V supply
• Green LED on the LSB module constantly lit, red LED flashes
– LSB module without address
– No or incorrect parameters activated
• Green and red LED on the LSB module constantly lit
– Incorrect address set on the LSB module