EasyManuals Logo
Home>Lamtec>Transmitter>KS1D

Lamtec KS1D Quick Reference

Lamtec KS1D
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #84 background imageLoading...
Page #84 background image
83
10 Options
10.5.1 Commissioning of the Additional Modules
Checking the module
Ensure that the CAN LOW and CAN HIGH, as well as the 24V voltage supply, are con-
nected correctly.
Make sure that a terminal resistance of 120 
is set at the free connecting point between CAN LOW and CAN HIGH.
Setting the address on the module (tens at the top, ones at the bottom)
– LSB module with 4 analogue outputs: LSB address 19
– LSB module with 4 digital outputs: LSB address 03
– LSB module with 4 digital inputs: LSB address 11 – Modules for calculating the efficiency
or field bus connection do not require
an own LSB address
With digital modules, the switches of the manual operating levels must be set to "A."
After switching on, you should see the following status
Red LED off on the LSB module
Green LED flashes on the LSB module
If not, consider the following problem solutions
No LED on the LSB module lit
No 24V supply
Green LED on the LSB module constantly lit, red LED flashes
LSB module without address
No or incorrect parameters activated
Green and red LED on the LSB module constantly lit
Incorrect address set on the LSB module

Table of Contents

Other manuals for Lamtec KS1D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec KS1D and is the answer not in the manual?

Lamtec KS1D Specifications

General IconGeneral
BrandLamtec
ModelKS1D
CategoryTransmitter
LanguageEnglish

Related product manuals