10. Technical data
Main features
Keor
MOD
25
Keor
MOD
50
Keor
MOD
75
Keor
MOD
100
Keor
MOD
125
Keor
MOD
150
Keor
MOD
175
Keor
MOD
200
Keor
MOD
225
Keor
MOD
250
Nominal Power
(kVA)
25 50 75 100 125 150 175 200 225 250
Active Power
(kW)
25 50 75 100 125 150 175 200 225 250
Number of power
modules
1 2 3 4 5 6 7 8 9 10
Technology
online, double conversion
VFI-SS-111 (EN62040-3)
IN/OUT conguration Three-phase / Three-phase
Dual Input Available
UPS system Modular, expandable and redundant
Neutral system Neutral passing straight from input to output (not isolated)
Bypass
Automatic (static and electromechanical)
Manual (for maintenance)
Overvoltage category OVC II
Input electrical characteristics
Keor
MOD
25
Keor
MOD
50
Keor
MOD
75
Keor
MOD
100
Keor
MOD
125
Keor
MOD
150
Keor
MOD
175
Keor
MOD
200
Keor
MOD
225
Keor
MOD
250
Rated input current (A)
(full load and 400V
input voltage)
37.6 75 113 150 188 225.6 263.2 300 338 376
Maximum input
current (A)
(full load and 320V
input voltage)
47 94 141 188 235 282 329 376 423 470
Input voltage
(V)
400 + 15% - 20%
(3F+N+PE)
Input frequency
(Hz)
50 / 60 ± 2%
50 / 60 ± 14 %
(autosensing and/or selectable by the user)
Input Power Factor > 0.99
Total harmonic distortion
of the input current
THDi < 3% (at full load)
Icp
Prospective short-circuit
current (kA)
10