Page 13
SPECIFICATIONS - GAS HEAT - 094U, 122U, 152U
Heat Input Type Standard Medium High
Number of Gas Heat Stages 2 2 2
Gas Heating
Performance
Input - Btuh First Stage 84,500 117,000 156,000
Second Stage 130,000 180,000 240,000
Output - Btuh Second Stage 104,000 144,000 192,000
Temperature Rise Range - °F 15 - 45 30 - 60 40 - 70
Thermal Efciency 80% 80% 80%
Gas Supply Connections 3/4 in. npt 3/4 in. npt 3/4 in. npt.
Recommended Gas Supply
Pressure - in. w.g.
Natural 7 in. w.c. 7 in. w.c. 7 in. w.c.
LPG/Propane 11 in. w.c. 11 in. w.c. 11 in. w.c.