23
EDBSV571 EN 1.0
EN
Commissioning
4.5.2 I/O Setup Parameters
Code Possible Settings
IMPORTANT
No. Name Default Selection
P121
TB-1 Digital Input 0 0 MODE dependent If P100 = 0 (Local) or = 2 (Network) then
P121=0 will have no function.
If P100 = 1 (Terminal), then P121 = 0 will
function as RUN/STOP.
1 STOP (when open, all modes) When TB1 is asserted, Local modes have no
function, Terminal mode has RUN function.
2 External Fault F.EF Normally closed circuit; open to trip
3 Inverse External Fault F.EF Normally open circuit; close to trip
4 Jog Forward Jog Forward speed = P134
5 Jog Reverse Jog Reverse speed = P135
Active even if P112 = 0
6 Preset Speed #1 For frequency mode see P131...P137,
For PID mode, see P231…P233,
For torque mode see, P331…P333
7 DC Brake Refer to P174; close input to override P175
8 Auxiliary Ramp to Stop Normally closed: Opening input will ramp
drive to STOP according to P127, even if P111
is set to Coast (0 or 1).
9 Clear Fault Close to reset fault
10 Accel/Decel #2 Refer to P125, P126
WARNING
Jog overrides all STOP commands! To stop the drive while in Jog mode, the Jog input must be
deactivated or a fault condition induced.
WARNING
To use Automatic Restart (power up start), set P110 to a restart setting; P100 = 1 (Terminal mode);
P121=1; and assert TB1.
P125
Acceleration Time 2 20.0 0.0 {s} 3600 • Selected using TB-13A...TB-13D (P121...
P124 = 17)
• For S-ramp accel/decel, adjust P106
P126
Deceleration
Time 2
20.0 0.0 {s} 3600
p127
Deceleration Time
for Auxiliary Ramp
to Stop
20.0 0.0 {s} 3600 • Selected using TB-13A...TB-13D (P121...
P124 = 19).
• For S-ramp accel/decel, adjust P106
• Once executed, this ramp time has priority
over P105 and P126.
p129
Automatic Accel/
Decel rate switch
threshold
0.0 0.0 {Hz} 1000 If Actual Frequency < P129 Use Accel/decel
time #2 (P125/P126)
If Actual Frequency > P129 Use Accel/decel
time #1 (P104/P105)