V6-i VRF 50/60Hz
105
Part
6 - Diagnosis and Troubleshooting
2.14 H7: Unmatched total number of indoor units
Digital display output 2.14.1
Description 2.14.2
Number of indoor units detected by the outdoor unit not same as number set on main PCB.
All units stop running.
Error code is displayed on the outdoor unit.
Trigger / recover condition 2.14.3
Trigger condition: Only one indoor unit cannot be detected by the outdoor unit for 8 hours or more than one indoor
unit cannot be detected by the outdoor unit for 3 minutes.
Recover condition: Number of indoor units detected by the outdoor unit is same as number set on main PCB.
Reset method: Resume automatically.
Possible causes 2.14.4
Number of indoor units set on main PCB not same as actual number of indoor units.
Some indoor units are powered off.
Communication wires between indoor and outdoor units not connected properly.
Indoor unit PCB damaged.
Indoor unit without address or indoor unit address duplicated.
Main PCB damaged.

Table of Contents

Other manuals for Midea V6-i Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea V6-i Series and is the answer not in the manual?

Midea V6-i Series Specifications

General IconGeneral
BrandMidea
ModelV6-i Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals