Midea V6-i Series Service Manual
2.6 E7: Temperature sensor (T7C1/2) error
Digital display output 2.6.1
Description 2.6.2
A compressor top temperature sensor or discharge pipe temperature sensor (T7C1/2) error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.6.3
Trigger condition: Discharge pressure 3MPa and discharge temperature < 15
o
C for 2 minutes.
Recover condition: Discharge pressure and temperature go back to normal.
Reset method: Manually restart.
Possible causes 2.6.4
Temperature sensor not connected properly or has malfunctioned.
Damaged main PCB.