V6-i VRF 50/60Hz
75
Part
6 - Diagnosis and Troubleshooting
Procedure 2.3.5
E2
Communication wires P Q E have short
circuited or disconnected
1
Yes
Reconnect the communication wires
No
Communication wires P Q E are not
connected in a daisy chain
Yes
Connect the communication wires in a
daisy chain
No
IDU power supply is abnormal
Yes
Ensure normal power supply
No
Wires between outdoor main PCB and
electric control box communication
terminals block are loose
Yes
Ensure the wires are connected properly
No
Interference from high voltage (220V or
higher) wires
Yes
Ensure the communication wires and
high voltage wires are separated
No
Communication wires are close to a
source of electromagnetic radiation such
as transformer or strong fluorescent lamp
Yes
Remove the source of interference, or
add additional shielding to the
communication wires
No
The length of communication wire is over
1200m
Yes
Reduce the wire length to less than
1200m or strengthen the signal
No
Replacing outdoor main PCB resolves the
error
No
Replace electric control box
communication terminals block
Notes:
1. Measure the resistance among P, Q and E. The normal resistance between P and Q is 120Ω, between P and E is infinite, between Q and E is infinite.

Table of Contents

Other manuals for Midea V6-i Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea V6-i Series and is the answer not in the manual?

Midea V6-i Series Specifications

General IconGeneral
BrandMidea
ModelV6-i Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals