V6-i VRF 50/60Hz
75
Part
6 - Diagnosis and Troubleshooting
Procedure 2.3.5
Communication wires P Q E have short
circuited or disconnected
1
Reconnect the communication wires
Communication wires P Q E are not
connected in a daisy chain
Connect the communication wires in a
daisy chain
IDU power supply is abnormal
Ensure normal power supply
Wires between outdoor main PCB and
electric control box communication
terminals block are loose
Ensure the wires are connected properly
Interference from high voltage (220V or
higher) wires
Ensure the communication wires and
high voltage wires are separated
Communication wires are close to a
source of electromagnetic radiation such
as transformer or strong fluorescent lamp
Remove the source of interference, or
add additional shielding to the
communication wires
The length of communication wire is over
1200m
Reduce the wire length to less than
1200m or strengthen the signal
Replacing outdoor main PCB resolves the
error
Replace electric control box
communication terminals block
Notes:
1. Measure the resistance among P, Q and E. The normal resistance between P and Q is 120Ω, between P and E is infinite, between Q and E is infinite.