Installation
*INSTALLATION*
131
Priming the circu-
lation pump
The gaps between a built-in machine and adjacent cabinetry
must not be sealed, e.g., with silicone sealant, as this could com-
promise the priming of the circulation pump.
Protective foil/
countertop pro-
tector
The protective foil supplied protects the countertop from damage
caused by steam when the door is opened. It should be positioned
underneath the countertop above the machine door.
Electromagnetic compatibility (EMC)
The machine has been tested for electromagnetic compatibility (EMC)
in accordance with EN61326-1 and is suitable for operation in com-
mercial environments, such as hospitals, medical practices, and labo-
ratories plus other similar environments which are connected to the
domestic electrical supply.
The machine’s high frequency (HF) energy emissions are very low and
are therefore unlikely to interfere with other electronic machines in the
vicinity.
Flooring in the installation area must be wood, concrete, or tiled. Syn-
thetic flooring must be able to withstand a relative humidity level of at
least 30% to minimize the risk of electrostatic discharges.
The quality of the power supply should comply with that found in a
typical commercial or hospital environment. Check that the power
supply voltage is within a range of +/-10% of its nominal value.

Table of Contents

Other manuals for Miele PG 8581

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Miele PG 8581 and is the answer not in the manual?

Miele PG 8581 Specifications

General IconGeneral
Model NumberPG 8581
BrandMiele
ColorStainless Steel
ProgramsMultiple programs
Dimensions (H x W x D)835 mm x 600 mm x 600 mm

Related product manuals