PARAMETERS
91
z
Retry function (Pr. 65, Pr. 67 to Pr. 69)
Pr. 65 "retry selection"
Pr. 67 "number of retries at alarm occurrence"
Pr. 68 "retry waiting time"
Pr. 69 "retry count display erasure"
When an alarm occurs, the retry function causes the inverter to automatically reset itself to make a restart
and continue operation. You can select whether retry is made or not, alarms reset for retry, number of retries
made, and waiting time.
Parameter
Number
Factory Setting Setting Range
65 0 0 to 5
67 0 0 to 10, 101 to 110
68 1 s 0 to 10 s
69 0 0
<Setting>
Use Pr. 65 to select alarms to be reset for retry.
Errors Reset for Retry Setting
Display 012345
E.OC1
zz zzz
E.OC2
zz zz
E.OC3
zz zzz
E.OV1
zzzz
E.OV2
zzzz
E.OV3
zzzz
E.THM
z
E.THT
z
E.IPF
zz
E.UVT
zz
E.FIN
E. BE
zz
E. GF
zz
E. LF
E.OHT
z
E.OLT
zz
E.OPT
zz
E.OP1
zz
E.OP2
zz
E.OP3
zz
E. PE
zz
E.PUE
E.RET
E.CPU
E.E6
E.E7
E.MB1
zz
E.MB2
zz
E.MB3
zz
E.MB4
zz
E.MB5
zz
E.MB6
zz
E.MB7
zz
E.P24
E.CTE
Note:
z
indicates the errors selected for retry.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric FR-A520-0.4K -55K and is the answer not in the manual?

Mitsubishi Electric FR-A520-0.4K -55K Specifications

General IconGeneral
BrandMitsubishi Electric
ModelFR-A520-0.4K -55K
CategoryInverter
LanguageEnglish

Related product manuals