9
–
+
CN560
TB530
R2
R2
R1
R1
C
+
–
TB571
SW502
SW500
11. Setting Signal Output
■ Connecting the SYSTEM CONTROL Interface
Each relay can be turned ON/OFF by synchronizing with the room air conditioner’s ON/OFF, error/normal, Heater
ON/Heater OFF, and Humidifier ON/Humidifier OFF.
Indoor unit
Interface unit
➊
(Gray) (Sky
Blue)
DC power supply: DC 12 V (+10 %, -0 %) 5 W or more. Please use
power supply with double insulation or reinforced insulation.
DC 12 V
power
supply
Relay 2
Relay 1
Relay 1, 2:
(Coil rating of DC 12 V, 1.0 W or
less.) Please use relays with
reinforced insulation.
Screw
driver
Do not insert more than one
connecting cable into each
terminal of TB571 and TB530.
● For TB571 and TB530, insert wiring after inserting the flathead screwdriver into the terminal.
●
Appropriate electric wire for TB571 and TB530 is as follows. Stranded wire: 0.3 mm
2
to 1.25 mm
2
[AWG 22 to 16] Solid wire: ø 0.4 mm to ø 1.2 mm
[ø 1/64 in. to ø 3/64 in.]
● Peeling dimension of the electric wire for TB571 and TB530 is 7 mm to 10 mm [9/32 in. to 25/64 in.].
● Wiring length from the interface to Relay 1 and Relay 2 should be less than 50 m [164 ft.].
■ Setting when using Status Signal Output
Terminal
Notes
•
Connecting terminal TB530 for power supply is polarized, so confirm proper polarity of the terminals before connecting.
• Do not connect DC 12 V from the DC power supply to TB571.
• Confirm polarity when using a diode built-in relay. C of TB571 is electropositive potential
, and R1 and R2 are negative potential .
Functions SW No. Operating details
ON/OFF,
Error/
Normal
Output
SW502
ON
OFF
12345678
12345678
SW500
ON
ON
SW502-1: OFF
• Relay 1 is on when room air conditioner is on, and off when room air conditioner is off.
• Relay 2 is on when room air conditioner is in error, and off when room air conditioner is operating normally.
SW502-1: ON
• Relay 1 and 2 behavior are opposite of those above.
ON/OFF,
Heater
Control
Output
SW502
ON
OFF
12345678
12345678
SW500
ON
ON
SW502-1: OFF
• Relay 1 is on when room air conditioner is on, and off when room air conditioner is off.
•
When the air conditioner runs in the heating (automatic heating) mode and room temperature becomes the set tem-
perature - 2.5 ºC (4.5 ºF) or lower, the Relay 2 (heater) turns on.
When the air conditioner runs in a mode other than the heating (automatic heating) or it is OFF, or when room tem-
perature becomes the set temperature or higher, the Relay 2 (heater) turns off.
SW502-1: ON
• Relay 1 and 2 behavior are opposite of those above.
ON/OFF,
Humidifier
Control
Output
SW502
ON
OFF
12345678
12345678
SW500
ON
ON
SW502-1: OFF
• Relay 1 is on when room air conditioner is on, and off when room air conditioner is off.
•
When the air conditioner runs in the heating (automatic heating) mode, Relay 2 (humidifier) turns on. When the air
conditioner runs in a mode other than heating (automatic heating) or it is OFF, Relay 2 (humidifier) turns off.
SW502-1: ON
• Relay 1 and 2 behavior are opposite of those above.
Heater
Control,
Humidifier
Control
Output
SW502
ON
OFF
12345678
12345678
SW500
ON
ON
SW502-1: OFF
• When the air conditioner runs in the heating (automatic heating) mode and room temperature becomes
the set temperature - 2.5 ºC (4.5 ºF) or lower, Relay 1 (heater) turns on. When the air conditioner runs in a
mode other than the heating (automatic heating) or it is OFF, or when room temperature becomes the set
temperature or higher, Relay 1 (heater) turns off.
•
When the air conditioner runs in the heating (automatic heating) mode, Relay 2 (humidifier) turns on. When the air
conditioner runs in a mode other than heating (automatic heating) or OFF, Relay 2 (humidifier) turns off.
SW502-1: ON
• Relay 1 and 2 behavior are opposite of those above.
ON/OFF,
Heater
Control
(single
operation)
Output*
SW502
12345678
12345678
SW500
ON
ON
Relay 1 is on when ON is set by System controller, ME remote controller or MA remote controller, and off
when OFF is set by these controllers.
When room temperature becomes the set temperature or lower in the heating (automatic heating) mode,
the Relay 2 (heater) turns on. When a mode other than heating (automatic heating) or OFF is set by System
controller, ME remote controller or MA remote controller, or when room temperature becomes higher than
the set temperature + 1 ºC (2 ºF), the Relay 2 (heater) turns off.
* This function is to run the heater instead of the air conditioner in the heating mode. The air conditioner
stops in the heating mode.
Do not use the remote controller attached to the air conditioner. If you use it, the operation may not reflect
the setting.
The position of detecting the room temperature is where MA remote controller is put, so make sure to
connect it to the interface unit.
Please use the cable of 0.5 mm
2
[AWG 20] or more.
The cable must fit into TB530 and meet DC 12 V power supply.
JG79Y451H01EN.indd9 2018/06/1317:01:55