Page #63 background imageLoading...
Page #63 background image
63
How long is “PLEASE WAIT”
kept being displayed on the
remote controller?
6 minutes
or more
2 minutes
or less
2 to 6
minutes
NO
NO
YES
YES
Are any error codes
displayed on the
remote controller?
Are any error codes
displayed on the LED?
Symptoms: “PLEASE WAIT” is kept being displayed on the remote controller.
Check the display time of “PLEASE WAIT”
after turning on the main power.
“PLEASE WAIT”
will be displayed
during the start-up
diagnosis after turning
on the main power.
• Normal.
The start-up diagnosis will
be over in around 2 minutes.
• Mis-wiring of indoor/
outdoor connecting
wire
• Breaking of indoor/
outdoor connecting
wire (S3)
• Defective indoor
controller board
• Defective outdoor
controller circuit
board
• Refer to “Self-diagnosis
action table” in order to
solve the trouble.
• In case of communication
errors, the display of
remote controller may not
match the LED display of
the outdoor unit.
• Defective indoor
controller board
• Defective remote
controller
Check the LED display of the
outdoor controller circuit board.
Diagnosis flow Cause
Inspection method and
troubleshooting
OCH415G

Table of Contents

Other manuals for Mitsubishi Electric PUHZ-P125YHA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric PUHZ-P125YHA and is the answer not in the manual?

Mitsubishi Electric PUHZ-P125YHA Specifications

General IconGeneral
BrandMitsubishi Electric
ModelPUHZ-P125YHA
CategoryAir Conditioner
LanguageEnglish

Related product manuals