687
V MULTI
(c) Calculation of total operation characteristics
Since the operation characteristics of series Multi depend on combination of indoor unit, calculate the total operation charac-
teristics of the system by using the formulas below according to specifications of each indoor unit or outdoor unit.
1)Total power input
Total power input (kW) = Power input of outdoor unit + (Power input of indoor unit)
2)Total running current
Total running current (A) = Running current of outdoor unit + [ (Running current of indoor unit) × 2/3]
3)Total power factor
Total power factor (%) = [Total power input (W) /
3 × Total running current (A) × Power source] × 100
Total operation characteristics = Operation characteristic value of outdoor unit + Operation characteristic value of indoor unit
[Example]
(3) Operation chart
The Multi series is a system that allows for different models and capacities of indoor units to be combined so the individual
operating characteristics of the indoor and outdoor are provided. Use the procedure shown in Item (c) to calculate the combined
operating characteristics.
(a) Operating characteristic of outdoor unit
Cooling input
Heating input
Cooling running current
Heating running current
Inrush current (L.R.A)
Cooling power factor
Heating power factor
(380 V/415 V)
Item
Model
FDC508HES3
5.03/5.28
4.58/4.71
8.6/9.4
8.1/9.0
74
89/78
86/73
8.44/8.54
6.44/6.64
14.2/13.5
11.6/11.2
99
90/88
84/82
11.92/12.02
9.72/9.92
20.0/19.0
16.5/16.0
154
91/88
90/86
FDC808HES3 FDC1008HES3
kW
A
A
%
Note (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 UNITARY AIR-CONDITIONERS
(b) Operating characteristic of indoor unit
Item
Model FDT Series
FDT Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.10/0.11
0.5/0.5
0.11/0.12
0.6/0.6
0.21/0.21
1.2/1.2
0.27/0.27
1.4/1.4
208-A 258-A 308-A 408-A 508-A
Item
Model FDR Series
FDR Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.11/0.120.10/0.11
0.5/0.5
0.15/0.16
0.7/0.7
0.19/0.19
0.9/0.9
0.24/0.24
1.2/1.2
208-A 258-A 308-A 408-A 508-A
Notes (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 UNITARY AIR-CONDITIONERS
(2) The values shown in the above table are common to both cooling and heating operations.
(Conditions) Operation Voltage ········Indoor unit: 220 V, 50 Hz
Outdoor unit: 380 V, 50 Hz
Operation mode ···········Cooling and Heating
Unit·······························Outdoor unit: FDC808HES3 × 1 unit
Indoor unit: FDT308-A × 1 units, FDT508-A × 1 units

Table of Contents

Other manuals for Mitsubishi Heavy Industries FDT408-A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDT408-A and is the answer not in the manual?

Mitsubishi Heavy Industries FDT408-A Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDT408-A
CategoryAir Conditioner
LanguageEnglish

Related product manuals