V MULTI
(3) Outdoor unit
Model FDC508HES3
Required space for maintenance and air flow Minimum allowable space to the obstacles
Unit:mm
Mark
123
L1 Open Open 500
L2 300 5 Open
L3 150 300 150
L4 555
Installation
type
Notes
(1) Avoid the location where four sides are entirely
surrounded by walls.
(2) Fix the unit by anchor bolts without fail. Restrict
the protrusion length of anchor bolt to 15 mm
and under.
(3) When strong wind blows against the unit, direct
the discharge port at a right angle to the wind
direction.
(4) Secure the space of 1 m and over at the top of
unit.
(5) Make the height of obstruction wall in front of
discharge port lower than the height of unit.
VIEW A
L
2
L
3
L
4
L
1
Air
inlet
Air inlet
Air outlet
Maintenance
space
50
110
195
555
578
920
10
46
50
48
100
165
580
175
35
15
380 15
15
103
5050
50
50
110
195
50
70
50 15
50
27
50
15
47
295237
15
340
35
55
55
150
40
Gas piping:
φ
19.05 (3/4")
(Flare connecting)
Liquid piping:
φ
9.52 (3/8")
(Flare connecting)
Opening for electric wiring
Holes for drain
(
φ
20 × 3pcs.)
Opening for
electric wiring
Opening for piping
and electric wiring
Opening for piping
and electric wiring
Electric wiring
Opening for piping
and electric wiring
Holes for anchor bolt
(M10 × 4pcs.)
Gas piping:
φ
19.05 (3/4")
(Flare connecting)
Liquid piping:
φ
9.52 (3/8")
(Flare connecting)
Opening for electric wiring
Terminal block
1250
A
Unit: mm