77
-
2) During heating operation, the fan speed is controlled in accordance with the outdoor heat ex-
changer temperature (detected by Tho-R) and the outside air temperature (detected by Tho-A).
-3 0
35
12 15
Zone C
Zone A
Zone B
Outside air temperature (˚C)
Zone E
Outdoor heat exchanger temperature (˚C)
Zone D
Zone A Zone B Zone C
Zone D
Zone E
1th speed
1th speed
4th speed
4th speed
4th speed
4th speed
Tho-A
Tho-R
Notes (1) The temperature at whichever outdoor heat exchanger temperature thermistor (Tho-R1 or R2) has the lowest reading is detected.
22 25
26 44
46 55
Zone E
Zone C
Zone D
Outside air temperature (˚C)
Zone B
Outdoor heat exchanger temperature (˚C)
Zone A
Zone A Zone B
Zone C
Zone D
Zone E
4th speed
4th speed
2th speed
4th speed
2th speed
1th speed
Tho-A
Tho-R
Notes (1) The temperature at whichever outdoor heat exchanger temperature thermistor (Tho-R1 or R2) has the highest reading is detected.
3) The fan speed is controlled in accordance with the outdoor heat exchanger temperature (de-
tected by Tho-R) and the outside air temperature (detected by Tho-A) during cooling or dehu-
midifying.
4) Outdoor fan speed control during heating
a) If the fan starts when the outside air temperature (detected by Tho-A) is 12ºC or higher, the outdoor fan motor
runs at speed A for 4 minutes, then after 4 minutes control switches to the outdoor fan speed control in item 2).
b) Even if the outside air temperature (detected by Tho-A) drops below 12ºC during operation with the outdoor
fan motor OFF, the outdoor fan motor continues to run at 2th speed for 4 minutes.
ON
OFF
35
Outdoor air temperature (˚C)
(c) Snow protection fan control
If SW5-2 (SW3-2) on the outdoor unit PCB is turned ON, a full stop results. Then in the abnormal stop mode and with the
thermostat OFF units outdoor fan outdoor temperature at 3ºC or lower, the fan is run for 10 seconds at 6th speed once every 10
minutes [Hi tap (4th speed)] .
Note (1) Items is ( ) show in the case of models FDCA801, 1001.
Speed A
801H
1001H
1th speed
0th speed
Control speed
Model

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDURA301 and is the answer not in the manual?

Mitsubishi Heavy Industries FDURA301 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDURA301
CategoryAir Conditioner
LanguageEnglish

Related product manuals