Check for an air pocket in the dosing booster impeller chamber (see the enclosed Dosing Booster Manual):
Open the NetaJet™ 4G sampling outlet until a stable flow, free of air-bubbles, is obtained.
5) If the original hydraulic conditions are still not restored - loosen the dosing booster's bleeding screw
and wait until a stable flow, free of air-bubbles, is obtained, then retighten the bleeding screw
(
see the enclosed Dosing Booster Manual
).
6) Check the dosing booster's impeller chamber for clogging:
If it is clogged - it should be dismantled and thoroughly cleaned (see the enclosed Dosing Booster Manual).
If after implementing all the above steps the malfunction is still not fixed - consult your Netafim
™
representative.