28
Temperature control
If you have not installed an after-heating element, use the settings to control the bypass damper.
It is necessary to install an after-heating element if you want to control the supply air temperature and for it to contribute towards the
heating of the dwelling. An after-heating element allows you to control the supply air temperature, regardless of the outdoor temper-
ature.
You can install an external electrical or water after-heating element in the supply air duct.
> Temp. regulation
Language
The default language for the ventilation unit is Danish. You can change the texts to other languages in the settings menu.
> Language (DK - Sprog)
ATTENTION
During periods when heating is not required in the dwelling, the supply air temperature may fall below the minimum
temperature.
> Min. supply air summer Settings:
Standard setting:
Description:
5 16 °C
14 °C
Here you set the supply air temperature that you want the ven-
tilation unit to be able to provide, as a minimum, during sum-
mer, when the unit is in heating mode.
> Min. supply air winter Settings:
Standard setting:
Description:
14 22°C
16 °C
Here you set the supply air temperature that you want the ven-
tilation unit to be able to provide, as a minimum, during winter,
when the unit is in heating mode.
NB: Only possible if an after-heating element has been
installed.
> Max. supply air summer Settings:
Standard setting:
Description:
5 50°C
35 °C
Here you set the supply air temperature that you want the ven-
tilation unit to be able to provide, as a maximum, when heating
is required.
NB: This option is only shown if an after-heating element has
been installed and activated.
> Max. supply air winter Settings:
Standard setting:
Description:
5 50 °C
35°C
Here you set the supply air temperature that you want the unit
to be able to provide, as a maximum, during winter.
NB: This option is only shown if an after-heating element has
been installed and activated.
> Summer/vinter shift Settings:
Standard setting:
Description:
5 30 °C
12 °C
Here you set the temperature for the shift between summer
and winter operation.
• If the outdoor temperature is higher, the unit will operate in
summer mode
• If the outdoor temperature is lower, the unit will operate in
winter mode
> Dansk Description: Select the language you want on the panel.