Ecodesign data - Ventilation
* Specific energy consumption
** Annual heating saved
SEC* average climate
-40,6 kWh/(m
2
.a)
SEC* cold climate
-79,5 kWh/(m
2
.a)
SEC* warm climate
-15,7 kWh/(m
2
.a)
SEC-Class A
Type Two-way ventilation
unit for residential
Type of drive Variable speed drive
Type of heat recovery system Recuperative (counter-
flow heat exchanger)
Thermal efficiency of heat recovery 90%
Maximum flow rate
398 m
3
/h (100 Pa)
Electric power input of fan drive, including any motor control
equipment, at maximum flow rate
175,1W
Sound power level (LWA) 48 dB(A)
Reference flow rate
0,077 m
3
/s
(278,6 m
3
/h)
Reference pressure difference 50 Pa
SPI
0,23 W/(m
3
/h)
Central demand control 2,04
Maximum internal leakage 1,82%
Maximum external leakage 1,12%
Visual filter warning An alarm on the user
panel appears when fil-
ters need changing.
To maintain the perfor-
mance and energy effi-
ciency of the unit it is
very important to
change filters regularly
Disassembly instructions www.nilan.dk
AEC - annual electricity consumption
253 kWh/år (100 m
2
)
AHS** average climate
4630 kWh (100 m
2
)
AHS** cold climate
9057 kWh (100 m
2
)
AHS** warm climate
2093 kWh (100 m
2
)