54 AFP-200 Instruction PN 15511:F2 10/11/99
3.2.4 Password Change (3)
From the Program Change screen, you can display
the Password Change screen by selecting 3=PASS-
WORD. Select the password to change by typing *
or #, then enter the new password. As the new
Program or Status password is entered it displays on
the fourth line. To save the new password and return
to the Program Change screen, press Enter. To return
to the Program Change screen without changing the
password, press Backspace.
3.2.5 Message Change (4)
From the Program Change screen, you can display
the Message Change screen by selecting 4=MES-
SAGE. The Message Change screen lets you change
the 40-character “All Systems Normal” message.
The screen to the right shows a sample Message
Change screen display.
The first character on the third line blinks and may
be changed to any alphabetic character by using the
keypad, then pressing the right cursor. When all
characters are entered (up to 40), press Enter. Type a blank space in character position 20 or 21 so the words do
not run together on an 80-character printer.
3.2.6 Zone Change (5)
From the Program Change screen, you can display
the Change Zone Label screen by selecting
5=ZONES. The Change Zone Label screen lets the
user change the custom label assigned to Zones 1-89.
The screen to the right shows a sample Change Zone
Label screen.
Select a zone to change by entering the zone number
(01-99) in character positions 19 and 20 on the second line. For single digit numbers, enter a leading zero
before the digit (for example, enter 07 for zone 7). The existing (if any) zone label displays on line 4 of the
LCD display, characters 2 through 20. Character 1 on line 4 is blank to force a space between the device and
zone labels when they are linked on the printer. Enter or change the zone label, then press Enter to change the
zone label in memory and return to the Change Zone Label screen. If the zone is out of range, the software
ignores the Enter key. Pressing the left cursor key returns to the Program Change screen.
CHANGE@PASSWORD
*,NNNNN,E=PROGRAM
#,NNNNN,E=STATUS
SYS@NORMAL@MESSAGE
CHANGE@ZONE@LABEL
SELECT@ZONE@01-89:
ENTER@UP@TO@19@CHAR: