AFP-200 Instruction PN 15511:F2 10/11/99 9
1.5 Controls and Indicators
1.5.1 Membrane Panel
The AFP-200 membrane panel includes windows for the Liquid Crystal Display (LCD) and six LEDs. The
control panel has 21 keys, including a 12-key alphanumeric pad, similar to a telephone keypad. Slide-in labels
for the six LEDs and the four main operator switches are included. Refer to Figure 1 for the location of
switches and LEDs.
LED Indicators
• AC Power (green)
• System Alarm (red)
• Pre-Alarm Warning (yellow)
• Supervisory/Security (yellow)
• Alarm Silence (yellow)
• System Trouble (yellow)
Operational switches
• Acknowledge/Step
• Alarm Silence
• Drill
• System Reset (lamp test)
Service/program switches
• Twelve-key pad with 0-9, *, #
• Four cursor keys (Up, Down, Right, Left)
• ENTER key
1.5.2 Local Sounder
The piezo sounder provides unique sounds for alarm, trouble and supervisory/security conditions.
1.5.3 Output Circuits
The AFP-200 output circuits consist of four Class B (Style Y) Notification Appliance Circuits (NACs) or
releasing circuits (fully programmable).
1.5.4 Relays
The control panel includes three dry contact relays for system alarm, system trouble, and supervisory. Contacts
are rated 2 A at 30 VDC and 0.5 A at 30 VAC (resistive).