SLC LOOP SHIELD WIRING
A)
NOTE
:
maintain the continuity of the shield wire throughout the loop, BUT DO NOT connect to any devices.
Connect the shield wire to the outside of the control panel cabinet and the cabinet to Earth.
B)
NOTE
:
in this case, DO NOT allow the shield drain or shield foil to touch the cabinet.
For Style 6 field wirings, connect ONLY ONE END of the shield to the negative side of Channel A.
Maintain the continuity of the shield wire throughout the loop, BUT DO NOT connect to any devices.
Page 21 Installation Manual AM-6000-60001.VP
NOTIFIER ITALIA Rev. B.1 Doc. M-180.2-AM6000-ENG
CABINET
(+)
(-)
FOR SLC LOOP WHICH IS NOT CONTAINED IN PIPING OR METAL PIPING
CABINET
(+)
(-)
FOR SLC LOOP WHICH IS CONTAINED IN METAL PIPING OR IN CONDUIT