1.
2.
Rails Separation
Before mounting the system to the rack, select the way you wish to place the system. Pay attention
to the airflow within the rack cooling, connector and cabling options.
While planning how to place the system, review the following points:
Make sure the system airflow is compatible with your installation selection. It is important to
keep the airflow within the rack in the same direction.
In case there are cables that cannot bend within the rack or in case more space is needed for
cable bending radius, it is possible to recess the connector side or the FRU side by
3.15” (8cm) by optional placement of the system’s rails.
The FRU side is extractable. Mounting the sliding rail inverted to the system will allow you to
slide the FRU side of the system, in and out.
To mount the system into the rack:
Install 10 cage nuts (E) into the desired 1U slot of the rack: 4 cage nuts in the non-
extractable side and 6 cage nuts in the extractable side.
Installing the Cage Nuts
1 2
Mount both of the outer rails (C+D) into the rack (as illustrated below), and use 8 standard
pan-head screws (F) to fix them to the rack. Do not tighten the screws yet.
Mounting the Outer Rails into the Rack