SrcCh := 100,
RcvSize := 2,
DstDat := DstDat[0],
Option := InOption);
CASE State OF
1: // Execute Send.
SendExecute := TRUE;
IF (SendInstance.Done=TRUE) THEN
State := 2;
ELSIF (SendInstance.Error=TRUE) THEN
State := 99;
END_IF;
2: // Execute Rcv.
RcvExecute := TRUE;
IF (RcvInstance.Done=TRUE) THEN
State := 3;
ELSIF (RcvInstance.Error=TRUE) THEN
State := 99;
END_IF;
3: // Normal processing
Trigger := FALSE;
DoFinsTrigger:=FALSE;
99: // Abnormal processing
Trigger := FALSE;
DoFinsTrigger:=FALSE;
END_CASE;