A-1
Difference Between CS/CJ-series and
NX-series in FINS Routing
The FINS routing specification settings in the NX-series CPU Units differ from those in the CS/CJ-ser-
ies CPU Units by the following points:
• Communication when 0 is specified for the destination network address
• Operation of the routing table during Clear All Memory operation.
A-1-1
Communication When 0 Is Specified for the Destination Network
Address
The communication may vary depending on the CPU Unit as described below.
CPU Unit Operation
NX Series Routing of the network of the built-in EtherNet/IP port.
CS/CJ Series Routing of the network of the Communications Unit that has the smallest unit number among
the installed CS/CJ-series Special Units.
Appendices
A-2
NX-series CPU Unit FINS Function User's Manual (W596)